Panasonic PAW280MAH2 Provozní pokyny Strana 71

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 74
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 70
71
Control
3. On the CZ-CAPBC2 PCB, cut jumper “JP1”, in order to activate the 0–10 V demand control
mode for the external BMS. Make sure that all other jumpers remain intact.
4. On the CZ-CAPBC2 PCB, set switch S3 to “VOLTAGE” or “NO VOLTAGE”, depending on the
BMS digital input (DI) conguration.
Control via dry contacts (factory default)
= “NO VOLTAGE”
Control via 12 – 24 V DC signals
= “VOLTAGE”
12 –24 V DC
GND
5. Restore and fasten the upper mounting board in its original position.
6. On the terminal connector of Section C, located on the upper mounting board inside the
AHU Kit enclosure (see diagram below), connect the digital inputs (DI) as follows:
Heating start to COM and DI1
Cooling start to COM and DI2
Fan mode (free cooling) start to COM and DI3
All DI contacts open = Stop
Zobrazit stránku 70
1 2 ... 66 67 68 69 70 71 72 73 74

Komentáře k této Příručce

Žádné komentáře