General information and safety instructions
1.3 Safety instructions
WARNING
The following precautions need to be followed strictly, in order to avoid hazardous situations,
which could result in death or serious injury.
Electricshockorremayresultfrominadequateorincorrectinstallationorwiring
procedures.
System installation must only be performed by an experienced electrician.
Arrange installation at the dealer where the system was purchased or use a
professional installer.
System installation must be performed in strict accordance to the installation
procedures described in this document.
Damagetothecircuitbreakersmayresultfromincorrectelectricalwiring,insufcient
electrical circuit capacity or use with other electrical devices.
Always use a dedicated branch circuit for electrical wiring.
Strictly avoid using other electrical devices within the same electrical circuit.
Make sure the electrical circuit used has sufcient capacity.
Overheatingorremayresultifconnectionsorattachmentsarenotsecure.
Use the specied cables (type and wiring diameter) for the electrical connec-
tions, and securely connect the cables.
Run and fasten the cables securely so that external forces or pressure placed
on the cables will not be transmitted to the connection terminals.
Suffocation can result if refrigerant gas leaks and exceeds the limit density in a small
room.
Installation of the refrigerant piping must only be performed by an experienced,
qualied installer to minimize the risk of leaks.
Install so that even if refrigerant gas leaks into the room, it will not exceed the
limit density of 0.44 kg/m
3
, in accordance with the local regulatioins for facility
air conditioning equipment.
If the refrigerant gas concentration does exceed the limit density, do one of the
following:
install an opening in a neighbouring room
or install ventilation equipment triggered by gas leak detection sensors
or install an automatic pump-down system provided by the manufacturer of
the equipment
Poisonousgascanresultifrefrigerantgascomesintocontactwithre.
After installation of refrigerant pipes, perform a dry nitrogen gas sealing test to
check that there are no leaks.
Ventilate the work area if refrigerant gas leaks during installation.