5.Settherefrigerantcylinderontotheelectronicscale,thencorrectthehosethecylinderandtotheconnectionportforthe
electronicscale.(1)(2)
Precaution:
Besuretosetupthecylinderforliquidcharging.Ifyouuseacylinderequippedwithasiphontube,youcanchargetheliquid
withouthavingtoturnthecylinderaround
6.Removethecharginghoseofthemanifoldgaugefromthevacuumpumpadaptor,andconnectittotheconnectionportofthe
electronicscale.(2)(3)
7.Openthevalveoftherefrigerantcylinder,thenopenthechargingvalveslightlyandcloseit.Next,pressthecheckvalveofthe
manifoldgaugeandpurgetheair.(2)(4)(Watchtheliquidrefrigerantcloselyatthispoint.)
8.Afteradjustingtheelectronicscaletozero,openthechargingvalve,thenopenthevalveLoofthemanifoldgaugeandcharge
withtheliquidrefrigerant.(2)(5)(Besuretoreadtheoperatinginstructionsfortheelectronicscale.)
9.Ifyoucannotchargethestipulatedamount,operatetheunitinthecoolingmodewhilechargingalittleoftheliquidatatime
(about150g/timeasaguideline).Ifthechargingamountisinsufficientfromoneoperation,waitaboutoneminute,thenusethe
sameproceduretodotheliquidchargingagain.
Precaution:
Neverusethegassidetoallowalargeramountofliquidrefrigeranttobechargedwhileoperatingtheunit.
10.Closethechargingvalve,andafterchargingtheliquidrefrigerantinsidethecharginghose,fullyclosethevalveLoofthe
manifoldgauge,andstoptheoperationoftheunit.(2)(5)
11.Quicklyremovethecharginghosefromtheserviceport.(6)Ifyoustopmidwaythrough,therefrigerantthatisinthecyclewill
bedischarged.
12.Afterputtingonthecapsfortheserviceportandoperatingvalve,inspectaroundthecapsforagasleak.(6)(7)
Fig.13Re-chargingrefrigerant
10.4.6.Brazing
Asbrazingrequiressophisticatedtechniquesandexperiences,itmustbeperformedbyaqualifiedperson.
Inordertopreventtheoxidefilmfromoccurringinthepipeinteriorduringbrazing,itiseffectivetoproceedwithbrazingwhileletting
drynitrogengas(N2)flow.